Error Messages
C-139
Error #230: Bad table coordinate :%%
The 'Z' coordinate (table number) belongs to a table that does not exist in the
application, probably because of differences in the data structure between
master and slave.
Error #231: Bad row coordinate :%% in table #%%
The 'Y' coordinate (row number) does not exist in the table, probably because of
differences in the data structure between master and slave.
Error #232: Bad column coordinate :%% in table #%%
The 'X' coordinate (column number) does not exist in the table, probably
because of differences in the data structure between master and slave.
Error #233: No COS memory space was allocated to table #%%
There is no 'COS' column defined in the table.
Error #234: NOT enough Space for Differentiators (%% Bytes). Application DISABLED.
Each application needs at least 256 bytes, which are not available, for
differentiators.
Error #235: Warning: Short USER RAM: %% Bytes
In case the free space available for application is less than 2 Kbyte, the user is
notified that the running application is limited.
Error #236: Index is out of range : %% %%
The index in the user application has reached 256 or exceeded it.
Error #237: No application in FLASH memory or Application was stopped !!
Trying to get data from some table, while the application was not downloaded
or was stopped.
Error #238: Task '%%' does NOT exist !!
For system software developers only. Consult product group.
Error #239: No Delta COS Area Was Allocated To Column #%% in Table #%%
Trying to read COS of a column that does not have COS area. Improper use of
DB_Map application.
Error #240: Invalid Time Tag List: %% OR Events list: %%
error returned from sio_set_di_cos_en(): %%
May indicate system software problem. Consult product group.