For a 120 VAC, 60Hz application, the AC supply breaker should be rated for a continuous
current of no less than 15A, with a recommended rating of 20A.
For a 220 VAC, 50Hz application, the AC supply breaker should be rated for a continuous
current of no less than 15A, with a recommended rating of 20A.
The above breaker current ratings are per R56 guide lines for communications equipment.
DC Breaker Recommendation
For information involving the sizing of cables and DC power distribution, please refer to the
Motorola R56 standard Standards and Guidelines for Communication Sites (68P81089E50).
For each MTR3000 Base Station/Repeater, the DC supply breaker should be rated for a
continuous current of 20A.